NUT (Network UPS Tools)

NUT monitors a UPS and shuts machines down cleanly when the battery runs low. One host (the server) is cabled to the UPS by USB or serial and runs a driver plus upsd; every other machine runs upsmon as a client that connects to the server over TCP port 3493 and shuts down when told. Typical homelab use: a Proxmox node or small box owns the USB cable, and NAS, other nodes and VMs follow it.

Documentation: NUT user manual · upsmon.conf · nut.conf · Hardware compatibility list

Verification: MONITOR line syntax, the primary/secondary roles, SHUTDOWNCMD, and MODE values (none, standalone, netserver, netclient) were checked against the upsmon.conf and nut.conf man pages. Not verified: systemd unit names, upsd.conf LISTEN, the usbhid-ups example, upsc/upscmd/upsrw/upsdrvctl/nut-scanner usage, the Proxmox shutdown ordering, and permissions on Debian. No command was executed.

See also: apcupsd · Homelab · Proxmox VE Overview and Install · Proxmox Clustering and HA · Proxmox qm and pct · Prometheus · Grafana · UFW (uncomplicated firewall) · Wake-on-LAN · Docker-Compose


Files and Roles #

FILEONPURPOSE
/etc/nut/nut.confallMODE=: none (default, nothing starts), standalone, netserver, netclient
/etc/nut/ups.confserverDefine each UPS and its driver
/etc/nut/upsd.confserverupsd listen addresses, limits
/etc/nut/upsd.usersserverUsers and their roles (who may monitor, who may change settings)
/etc/nut/upsmon.confallWhat to monitor and how to shut down
/etc/nut/upssched.confoptionalTimer-based events (for example “run on battery 5 minutes, then…”)
MODEUSE
standaloneOne machine with the UPS cable, no remote clients
netserverMachine with the cable that also serves clients
netclientMachine with no cable, watches a remote server

Terms: the host that is cabled to the UPS and shuts down last (it must tell the UPS to cut power) is the primary; hosts that only follow are secondary. These replaced the older master and slave names (older versions need the old words, newer ones accept both).


Server Setup #

bash
sudo apt install nut nut-client nut-server
sudo nut-scanner -U                  # find USB UPS devices and print ups.conf stanzas
lsusb | grep -i -E 'apc|cyber|eaton|ups'

/etc/nut/nut.conf:

ini
MODE=netserver

/etc/nut/ups.conf:

ini
maxretry = 3

[myups]
    driver = usbhid-ups
    port = auto
    desc = "Rack UPS"
    # vendorid = 051d           # restrict to one device if you have several (value from lsusb)
    # pollinterval = 2

/etc/nut/upsd.conf:

ini
LISTEN 127.0.0.1 3493
LISTEN 192.168.20.2 3493        # the LAN address clients will use

/etc/nut/upsd.users:

ini
[monuser]
    password = <STRONG_PASSWORD>
    upsmon primary               # use "master" on NUT older than 2.8

[remote]
    password = <ANOTHER_PASSWORD>
    upsmon secondary             # use "slave" on NUT older than 2.8

[admin]
    password = <ADMIN_PASSWORD>
    actions = SET
    instcmds = ALL

/etc/nut/upsmon.conf:

ini
MONITOR myups@localhost 1 monuser <STRONG_PASSWORD> primary
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
FINALDELAY 5
NOTIFYCMD /usr/sbin/upssched
NOTIFYFLAG ONBATT SYSLOG+WALL
NOTIFYFLAG LOWBATT SYSLOG+WALL

MONITOR <UPS>[@HOST[:PORT]] <POWERVALUE> <USER> <PASSWORD> primary|secondary. POWERVALUE is how many power supplies of this machine the UPS feeds (usually 1). SHUTDOWNCMD can be written as separate quoted elements on newer versions (2.8.6+); a single string works everywhere. The user’s role in upsd.users must match the role in MONITOR.

Permissions (Debian/Ubuntu): config files should be root:nut, mode 0640, because they contain passwords.

bash
sudo chown root:nut /etc/nut/*.conf /etc/nut/upsd.users
sudo chmod 640 /etc/nut/*.conf /etc/nut/upsd.users

Start:

bash
sudo upsdrvctl start                                  # start the driver by hand first
sudo systemctl restart nut-driver.target nut-server nut-monitor
sudo systemctl enable nut-server nut-monitor
upsc myups@localhost

Unit names vary: on Debian/Ubuntu look at systemctl list-units 'nut*' (nut-server, nut-monitor, nut-driver@<UPS> or nut-driver-enumerator, nut-driver.target).

Open the port to the LAN only: sudo ufw allow from 192.168.20.0/24 to any port 3493 proto tcp (UFW (uncomplicated firewall)). NUT’s own protocol is not encrypted by default; keep it on a trusted VLAN or use TLS support if your build has it.


Client Setup #

On each machine that should follow the UPS:

bash
sudo apt install nut-client

/etc/nut/nut.conf:

ini
MODE=netclient

/etc/nut/upsmon.conf:

ini
MONITOR myups@192.168.20.2 1 remote <ANOTHER_PASSWORD> secondary
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
bash
sudo systemctl enable --now nut-monitor
upsc myups@192.168.20.2 ups.status

Order of shutdown on low battery: secondaries log off from the server and shut down, then the primary waits (HOSTSYNC) for them before it shuts down and the UPS cuts power. Set the wait with HOSTSYNC.


Commands #

COMMANDDESCRIPTION
upsc -l [<HOST>]List UPSes on a server
upsc <UPS>@<HOST>Show all variables
upsc <UPS>@<HOST> ups.statusStatus: OL online, OB on battery, LB low battery, CHRG charging, RB replace battery
upsc <UPS>@<HOST> battery.chargeBattery percent
upsc <UPS>@<HOST> battery.runtimeEstimated runtime in seconds
upsc <UPS>@<HOST> ups.loadLoad percent
upscmd -l <UPS>@<HOST>List instant commands the UPS supports
upscmd -u admin -p <PASS> <UPS>@<HOST> beeper.disableRun a command
upscmd -u admin -p <PASS> <UPS>@<HOST> test.battery.start.quickStart a battery self-test
upsrw -l <UPS>@<HOST>List writable variables
upsrw -s battery.charge.low=30 -u admin -p <PASS> <UPS>@<HOST>Set a variable
upsdrvctl start / stopStart/stop the driver(s)
upsd -c reloadTell upsd to re-read its config
upsmon -c reloadTell upsmon to re-read its config
upsmon -c fsdForce shutdown sequence now (use with care: it shuts hosts down)
nut-scanner -UScan USB devices
nut-scanner -NScan the network (SNMP/XML/NUT) with the right options

upsc over TCP needs no login for read-only variables; the commands that change something need a user from upsd.users.


Low-Battery Behaviour #

OPTIONWHEREMEANING
LB flagUPSThe UPS itself says “low battery”; upsmon shuts down on it
override.battery.charge.low, override.battery.runtime.lowups.confMake NUT consider “low” earlier than the UPS does, to leave time for slow shutdowns (Proxmox with many VMs)
MINSUPPLIESupsmon.confMinimum healthy power supplies before shutdown (redundant PSU setups)
FINALDELAYupsmon.confSeconds between the last warning and the shutdown
HOSTSYNCupsmon.confHow long the primary waits for secondaries
POLLFREQ, POLLFREQALERTupsmon.confPoll interval normally and when on battery

Example: shut down once runtime falls below 10 minutes, in ups.conf:

ini
[myups]
    driver = usbhid-ups
    port = auto
    override.battery.runtime.low = 600
    override.battery.charge.low = 40

Not every driver honours override.*; check the driver’s man page (man usbhid-ups).


Proxmox and Virtual Machines #

  • Install NUT on the node that has the USB cable and run netserver mode; other nodes and a NAS run netclient. See Proxmox VE Overview and Install and Proxmox Clustering and HA.
  • A node shutdown by shutdown -h now stops guests following their “Start/Shutdown order” and timeouts; set sensible shutdown timeouts per guest (qm set <VMID> --startup order=1,down=60, see Proxmox qm and pct).
  • Do not pass the USB UPS through to a VM if the node should survive or coordinate; if you must, pass it to a single VM and make that VM the server, and mind that it stops first.
  • In a cluster, losing quorum while nodes shut down one after another is normal; plan which node shuts down last and whether to expect fencing/HA to react.
  • Power-on after the outage: set BIOS “Restore on AC power loss: power on”, and use Wake-on-LAN for machines that stay off.

Docker Compose (NUT server) #

USB passthrough needs the device mapped in. Image and config paths differ by image, so read the image README before use.

yaml
services:
  nut:
    image: <NUT_SERVER_IMAGE>:<TAG>
    restart: unless-stopped
    devices:
      - /dev/bus/usb:/dev/bus/usb
    ports:
      - "192.168.20.2:3493:3493"
    volumes:
      - ./nut:/etc/nut:ro

Running NUT on the host is usually simpler and more reliable than in a container, because the shutdown must act on the host.


Metrics and Alerts #

  • Prometheus: use a NUT exporter that talks to port 3493 (see Prometheus), then graph battery.charge, ups.load, ups.status in Grafana.
  • Notifications: upsmon runs NOTIFYCMD for events (ONLINE, ONBATT, LOWBATT, COMMBAD, SHUTDOWN); upssched can wait a few minutes before reacting. Example upssched.conf:
ini
CMDSCRIPT /usr/local/bin/ups-event.sh
PIPEFN /run/nut/upssched.pipe
LOCKFN /run/nut/upssched.lock
AT ONBATT * START-TIMER onbatt-warn 60
AT ONLINE * CANCEL-TIMER onbatt-warn

Troubleshooting #

SYMPTOMCHECK
upsc says Error: Data staleDriver not running or crashed: sudo upsdrvctl start, journalctl -u nut-driver@myups (or nut-driver.target)
Can't claim USB devicePermissions or another process owns it. Replug, check udev rules in the package (/lib/udev/rules.d/62-nut-usbups.rules), sudo udevadm trigger, or user/group in ups.conf
Connection refused from a clientLISTEN address in upsd.conf missing, nut-server not running, or firewall blocks 3493
Login failed / Access deniedUsername or password mismatch; role in upsd.users does not match the MONITOR line; remember primary/secondary versus master/slave on older NUT
UPS shows OL but RBBattery needs replacement
Shutdown never happensupsmon not running (MODE=none in nut.conf), or SHUTDOWNCMD fails; test with upsmon -c fsd on a test machine only
Everything shuts down on a short blipoverride.battery.*.low too high, or UPS reports LB early; lengthen delays with upssched timers
UPS powers off before secondaries finishRaise HOSTSYNC, make the primary last, set override.battery.runtime.low larger
Config changes ignoredsudo systemctl restart nut-server nut-monitor and re-run upsdrvctl start; upsd -c reload
Unit names not foundsystemctl list-units 'nut*'; names differ between Debian releases and between packages
Run in foreground to debugsudo upsdrvctl -D start (extra -D for more detail), sudo upsd -D, sudo upsmon -D