apcupsd monitors APC UPSes (USB, serial, SNMP or network) and shuts the host down cleanly when the battery runs low. One host owns the cable and runs the daemon; other hosts can read its status over the built-in Network Information Server (NIS, TCP port 3551). For vendor-neutral UPS software see NUT (Network UPS Tools).

Project: apcupsd Documentation: apcupsd(8)

Verification: Not run against a live UPS. Config directive names and apcaccess usage follow the apcupsd manual from memory; check man apcupsd.conf, man apcaccess and man apcupsd on your version. Items marked (unverified) in particular need checking. Third-party tools (exporters, REST wrappers) are named as examples only.

See also: NUT (Network UPS Tools) · Homelab · REST APIs · Prometheus · Grafana · UFW (uncomplicated firewall) · Wake-on-LAN


Files and Roles #

FILEPURPOSE
/etc/apcupsd/apcupsd.confMain configuration
/etc/default/apcupsdDebian/Ubuntu: set ISCONFIGURED=yes or the service will not start
/etc/apcupsd/onbattery, offbatteryScripts run when the UPS goes on or off battery
/etc/apcupsd/commfailure, commokScripts run when communication with the UPS is lost or restored
/etc/apcupsd/doshutdownScript run when shutdown is triggered
/etc/apcupsd/apccontrolDispatcher that runs the event scripts above
/var/log/apcupsd.eventsEvent log

Install and Start #

bash
sudo apt install apcupsd
sudoedit /etc/default/apcupsd        # ISCONFIGURED=yes
sudoedit /etc/apcupsd/apcupsd.conf
sudo systemctl enable --now apcupsd
apcaccess status

Configuration #

Local USB UPS (/etc/apcupsd/apcupsd.conf):

ini
UPSNAME rack-ups
UPSCABLE usb
UPSTYPE usb
DEVICE
LOCKFILE /var/lock
POLLTIME 60
ONBATTERYDELAY 6
BATTERYLEVEL 20
MINUTES 5
TIMEOUT 0
NETSERVER on
NISIP 127.0.0.1
NISPORT 3551

Leave DEVICE empty for USB so apcupsd autodetects it.

DIRECTIVEMEANING
UPSCABLEusb, smart, simple, or ether for network
UPSTYPEusb, apcsmart, net (client of another apcupsd), snmp, pcnet, modbus
DEVICEEmpty for USB, serial port for serial, <HOST>:3551 for net
BATTERYLEVELShut down when charge falls to this percent
MINUTESShut down when estimated runtime falls to this many minutes
TIMEOUTShut down after this many seconds on battery (0 disables)
ONBATTERYDELAYSeconds on battery before the onbattery event fires
NETSERVERon enables the NIS server for remote apcaccess and clients
NISIPAddress NIS listens on; default is loopback only
NISPORTNIS port, default 3551

Shutdown fires on whichever of BATTERYLEVEL, MINUTES or TIMEOUT is reached first.

Network client (a second machine that follows the host that owns the cable):

ini
UPSNAME follower
UPSCABLE ether
UPSTYPE net
DEVICE 192.0.2.10:3551

Allow the LAN only, on the server: sudo ufw allow from 192.0.2.0/24 to any port 3551 proto tcp (UFW (uncomplicated firewall)). NIS is unauthenticated and unencrypted; keep it on a trusted VLAN and set NISIP to a specific address, not 0.0.0.0, where you can.


Commands #

COMMANDDESCRIPTION
apcaccessShow full status of the local UPS (same as apcaccess status)
apcaccess status <HOST>:3551Query a remote apcupsd NIS server
apcaccess -h <HOST>:3551Same, using the option form
apcaccess status | grep -E 'STATUS|LOADPCT|BCHARGE|TIMELEFT'Pick out the useful lines
apcaccess -uPrint values without units (easier to parse) (unverified on older versions)
sudo apctestInteractive hardware test and calibration (stop the daemon first: sudo systemctl stop apcupsd)
sudo systemctl restart apcupsdRe-read the configuration
journalctl -u apcupsdDaemon log
tail -f /var/log/apcupsd.eventsWatch power events
man apcupsd.confEvery directive for your version

Status Fields #

FIELDMEANING
STATUSONLINE, ONBATT, COMMLOST, plus flags such as LOWBATT, REPLACEBATT, CHARGING
LINEVInput line voltage
LOADPCTLoad as percent of capacity
BCHARGEBattery charge percent
TIMELEFTEstimated runtime remaining, in minutes
BATTVBattery voltage
NUMXFERSNumber of transfers to battery since start
TONBATTSeconds on battery in the current event
CUMONBATTCumulative seconds on battery
LASTXFERReason for the last transfer to battery
SELFTESTResult of the last self-test
MBATTCHGConfigured shutdown charge percent
MINTIMELConfigured shutdown runtime in minutes

Fields present vary by model and connection.


Event Scripts #

Create /etc/apcupsd/onbattery with your own actions, which override the stock script of the same name. The scripts run as root, so keep them short and quote everything.

bash
#!/bin/sh
logger -t apcupsd "UPS on battery"
curl -fsS -m 10 -d "UPS on battery" https://ntfy.example.com/ups || true
exit 0

Exit code 0 lets apcupsd carry on with its default action; exit 99 skips it (unverified; check man apccontrol).


Reading It over HTTP (REST) #

apcupsd has no built-in REST or HTTP API: its protocol is the NIS text protocol on TCP port 3551, read by apcaccess. To get at it from scripts or dashboards, use a wrapper. See REST APIs for calling the result.

APPROACHNOTES
apcaccess plus a scriptParse apcaccess status in a cron job or Prometheus textfile collector
apcupsd exporter for PrometheusThird-party exporter that queries port 3551 and serves /metrics over HTTP, then graph in Grafana
Home Assistant APC UPS Daemon integrationReads NIS directly; no wrapper needed
Small web serviceA few lines of Python or shell that run apcaccess and return JSON

Turn apcaccess into JSON in shell:

bash
apcaccess status | awk -F' *: ' '{printf "%s\"%s\":\"%s\"", sep, $1, $2; sep=","} BEGIN{printf "{"} END{print "}"}'

Then query it like any API, for example curl -s http://HOST:8080/ups | jq '{status: .STATUS, charge: .BCHARGE}'. Values keep their units (100.0 Percent); use apcaccess -u or strip them in the wrapper.


Troubleshooting #

SYMPTOMCHECK
Service exits straight awayISCONFIGURED=yes in /etc/default/apcupsd; journalctl -u apcupsd
STATUS : COMMLOSTUSB cable or UPSTYPE/UPSCABLE mismatch; lsusb, replug, check DEVICE is empty for USB
apcaccess says it cannot connectDaemon not running, NETSERVER on missing, or NISIP not the address you query
Remote apcaccess times outNISIP bound to loopback, or firewall blocks 3551
Shuts down too early or too lateBATTERYLEVEL, MINUTES and TIMEOUT; whichever is hit first wins
Config changes ignoredsudo systemctl restart apcupsd
Event scripts do not runExecutable bit, shebang, and that the filename matches a stock event name
Need low-level testsudo systemctl stop apcupsd && sudo apctest